EFFECTIVE COMPRESSION AND SHEAR AREAS FOR GROUTED MASONRY UNITS



The effective area of hollow masonry used in design vary and are generally dependent upon the thickness of the face shells and the cross-webs, the width of grouted core, and the type of mortar bedding used in construction. Since contractors may use standard two-hole (plain or concave ends) or open-end concrete masonry units, and since exact configuration may vary between manufacturers, the precise effective area will be unknown at the time of design. Effective areas for masonry walls loaded in compression or in shear parallel to the wall are given in the table below. Adjustments need to be made to reflect loss of area resulting from the use of reglets, flashing, slip-joints, and raked mortar joints. Values provided are in2 per linear foot.

Spacing of Grouted Cells Nominal Wall Thickness
6 8 10 12
Fully Grouted 68 92 116 140
16 44 59 72 85
24 38 49 59 68
32 34 44 52 60
40 32 42 48 55
48 31 40 46 52
56 30 38 44 50
64 29 37 43 48
72 28 36 42 47
No Grout 24 30 33 36


Try Our Message Board


Bringing Efficiency to the Construction Industry
EPC Server.com
Copyright © 2001,2002, EPCServer.com All rights reserved. All content in this site is provided 'as is' and no warranty is given as to the accuracy or suitability of any part hereof. No liability will be accepted for any direct or consequential losses, howsoever caused, following the use or misuse of any advice or information, real or implied, provided by this site.